Permit: T07EL01399

Parcel: 112052070

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/24/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ITEMS 2, 3, 5, 7 FROM INSPECTION ON 7/31/07
07/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BREAKERS LISTED FOR USE IN G.E PANEL
NEC 110.3
2. PROPERLY BOND AROUND REDUCING WASHERS -
NEC 250.96
3. INSTALL ANTI-OXIDATION COMPOUND AT ALUMINUM CONNECTIONS
4. FLEXIBLE METAL LIQUID TIGHT CANNOT BE USED AS EQUIPMENT GROUND. LOCAL AMENDMENT.
5. REMOVE PAINT AT GROUND CLAMP CONNECTION AT
GAS PIPE - NEC 250.12
6. IF CLAMP FOR GAS PIPE TO BE BELOW GRADE NEEDS TO BE LISTED & MARKED FOR DIRECT BURY
7. PLEASE VERIFY WATER BOND
8. LIQUID TIGHT CONNECTION AT PANEL BREAKING OUT CONCENTRICS
9. CANNOT SEE INTO METER SECTION. SERVICE
ENERGIZED & SEALED PRIOR TO APPROVALS.