Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/08/2007 | ELECTRIC - FINAL | Approved | ||
| 08/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE EQUIPMENT & GROUND - NEC 250.32 2. POINT OF ATTACHMENT TO BE BELOW WEATHERHEAD NEC 230 3. NEED BUSHING FOR PVC - NEC 352 4. IDENTIFY DISCONNECT - NEC 110 5. PLAN CALLS FOR 125 AMP FEEDER - TRIPLEX & OVERCURRENT PROTECTION TO HAVE PROPER AMPACITY NEC 310.20, 240 6. DISCONNECT ABANDONED FEEDERS FROM SOURCE 7. UNDERGROUND SPLICE CONNECTORS TO BE AL/CU AND WET LOCATION LISTED - NEC 110 8. CONDUCTORS TO BE MARKED -- NEC 310.11 |