Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE VERIFY PERMIT FOR NEW A/C 2. SUPPORT CONDUIT ABOVE PANEL 3. CORRECTLY IDENTIFY GROUNDED & GROUNDING CONDUCTORS 4. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 5. CORRECTLY LABEL PANEL AS PER 408.4 6. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 7. PROPERLY SUPPORT AC DISCONNECT |