Permit: T07EL01387

Parcel: 121061810


Addresses:

1516 N VAN BUREN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/29/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE VERIFY PERMIT FOR NEW A/C
2. SUPPORT CONDUIT ABOVE PANEL
3. CORRECTLY IDENTIFY GROUNDED & GROUNDING CONDUCTORS
4. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT
5. CORRECTLY LABEL PANEL AS PER 408.4
6. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE
7. PROPERLY SUPPORT AC DISCONNECT