Permit: T07EL01386

Parcel: 131041730

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SIZE SERVICE CONDUCTORS FOR 200 AMP SERVICE
NEC 310.15
2. MIN. HEIGHT OF POINT OF ATTACHMENT IS 10' - NEC 230.26
3. INSTALL LISTED MAST BRACING -- NEC 230.28
4. INSTALL 2 GROUND RODS MIN 6' APART - NEC 250.56
5. BOND GAS & WATER PER NEC 250.104
6. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL
7. PROVIDE ACCESS TO UTILITY ROOM FOR INSPECTION OF NEW ROMEX WIRES RUN TO EXISTING CIRCUITS
8. INSTALL PROPER SIZE PIPE STRAPS FOR RISER
9. WILL NEED MIN. 12' CLEARANCE ON SERVICE CONDUCTORS ACROSS YARD TO GRADE - NEC 230.24 & 230.26