Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - BONDING TYPE LOCKNUTS OR BOND BUSHINGS REQUIRED AT SECONDARY TERMINATIONS AT CT CAN PER 250.92 - BOND BLD. STEEL PER 250.104C |
|
| 09/18/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CT CAN LOCKED MUST BE OPEN FOR INSPECTION, HAVE APPROVED PLANS PERMIT ON SITE, OPEN ALL EQUIP. |