Permit: T07EL01372

Parcel: 14027046F


Addresses:

2660 E GANLEY RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- BONDING TYPE LOCKNUTS OR BOND BUSHINGS REQUIRED AT SECONDARY TERMINATIONS AT CT CAN PER 250.92
- BOND BLD. STEEL PER 250.104C
09/18/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CT CAN LOCKED
MUST BE OPEN FOR INSPECTION, HAVE APPROVED PLANS
PERMIT ON SITE, OPEN ALL EQUIP.