Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2007 | ELECTRIC - FINAL | Approved | ||
| 07/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CLEARANCE PER NEC 2005 110.26 IN FRONT OF ELECTRICAL IS 30" WIDE FROM CENTER OF EQUIPMENT AND 3' OUT GAS METER INTERFERES 2. NEW SERVICES REQUIRE 2 GRD. RODS 6' APART 3. WHERE IS YOUR WATER BOND 4. PLASTIC BUSHING NOT SET ON 3/4" ENTRY INTO PANEL 5. CLAMPS AT RISER ABOVE METER, FIRST ONE DOES NOT CLAMP AROUND PIPE, SECOND ONE DOES NOT REACH BACKING. 6. ENTRY AT BOTTOM RIGHT OF PANEL NOT INSTALLED IN A MECHANICALLY SOUND METHOD 7. USE PROPER FITTING INSIDE PANEL NOT CUT OFF CONNECTORS. |