Permit: T07EL01353

Parcel: 130101280


Addresses:

3158 E 25TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/27/2007 ELECTRIC - FINAL Approved
07/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SINCE RISER OVER 3' ABOVE ROOF AND DROP OVER 50' YOU ARE REQUIRED TO HAVE A BRACE FOR RISER ABOVE ROOF, USE A LISTED AND APPROVED TYPE.
2. STRAP GROUND WIRE BELOW SERVICE
3. IN ADDITION TO WATER BOND A GAS PIPE BOND ALSO REQUIRED.
4. THE 2-POLE CIRCUIT BREAKER MUST BE LISTED AND APPROVED TYPE NOT CONNECTED BY WIRE AT HANDLES
5. PANEL SCHEDULE TO BE FILLED OUT
6. CANNOT EXIT ENCLOSURE THRU TOP WALL FOR LOAD SIDE CONDUCTORS -- SEE LABEL
7. PERMANENTLY LABEL SERVICE WITH ADDRESS

ENERGIZED PRIOR TO APPROVAL