Permit: T07EL01349

Parcel: 125030120


Addresses:

3014 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/14/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/09/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. UNDER CABINET LIGHTING NOT IN
2. INSTA-HOT NEEDS DEDICATED CKT
3. INSTALL RANGE ANTI-TIP DEVICE & REMOVE BONDING JUMPER
4. INSTALL ALL LIGHT BULBS
5. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED
6. DEVICE COVERS MISSING
7. SMOKE DETECTOR IN HALL TOO CLOSE TO WALL - CHECK INSTALL INSTRUCTIONS
8. BOXES THAT SIT BACK MORE THAN 1/4" NEED EXTENDERS
9. MINI CANS NOT RATED FOR INSULATION CONTACT
10. ROMEX IN ATTIC TO BE RAN NEAT AND PROPERLY SECURED MUST BE PROTECTED BY ATTIC ACCESS

ALL WORK TO BE COMPLETE AND READY TO OCCUPY BEFORE CALLING IN FOR FINAL
09/12/2007 ELECTRIC - FINAL Cancelled IVRS - RI canceled
09/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HOUSE TO BE OPEN FOR INSPECTION
NO KEY ON TOP OF SERVICE
09/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING CANNOT USE MINERALLIC STRAP AND SMASHED EMT
2. BONDING JUMPERS TO BONDING BUSHINGS NOT SIZED PROPERLY NEC 250.102 & 250.122
3. PLEASE PROVIDE ACCESS TO INTERIOR OF UNIT