Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. UNDER CABINET LIGHTING NOT IN 2. INSTA-HOT NEEDS DEDICATED CKT 3. INSTALL RANGE ANTI-TIP DEVICE & REMOVE BONDING JUMPER 4. INSTALL ALL LIGHT BULBS 5. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED 6. DEVICE COVERS MISSING 7. SMOKE DETECTOR IN HALL TOO CLOSE TO WALL - CHECK INSTALL INSTRUCTIONS 8. BOXES THAT SIT BACK MORE THAN 1/4" NEED EXTENDERS 9. MINI CANS NOT RATED FOR INSULATION CONTACT 10. ROMEX IN ATTIC TO BE RAN NEAT AND PROPERLY SECURED MUST BE PROTECTED BY ATTIC ACCESS ALL WORK TO BE COMPLETE AND READY TO OCCUPY BEFORE CALLING IN FOR FINAL |
|
| 09/12/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 09/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HOUSE TO BE OPEN FOR INSPECTION NO KEY ON TOP OF SERVICE |
|
| 09/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING CANNOT USE MINERALLIC STRAP AND SMASHED EMT 2. BONDING JUMPERS TO BONDING BUSHINGS NOT SIZED PROPERLY NEC 250.102 & 250.122 3. PLEASE PROVIDE ACCESS TO INTERIOR OF UNIT |