Permit: T07EL01345

Parcel: 112053560


Addresses:

1942 E HEDRICK DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING AT GARAGE CEILING (ZIP CORD) NOT A PROPER WIRING METHOD, REMOVE OR CORRECT.
2. BEDROOMS - WIRING TO FAN (ZIP CORD) NOT A PROPER WIRING METHOD, REMOVE OR CORRECT.
3. BEDROOMS REQUIRE A SMOKE DETECTOR IN THEM
BATTERY OK, INSTALL PER MANUFACTURER LOCATIONS
4. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED
5. BATHROOM RECEPT. BY LAV TO BE GFI PROTECTED
6. INSTALL KITCHEN SWITCH (MISSING)
7. TWO OF THE TWENTY AMP CIRCUIT BREAKERS IN THE MAIN SERVICE PANEL D2 NOT SET CORRECTLY, THEY DO NOT CLIP ON BACK SIDE, THEY REMAIN LOOSE WHILE TURNING ON.
8. CIRCUIT BREAKER COVER NEEDS SCREWS

PLEASE CORRECT & RECALL