Permit: T07EL01344

Parcel: 135020670

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL01344

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/30/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT & MINNIE -- NEC 230.28
2. IDENTIFY NEUTRAL CONDUCTOR CLOSER TO WEATHERHEAD
3. INSTALL BREAKER LISTED FOR USE IN PANEL - NEC 110.3
4. USE CONNECTOR AT CABLE ENTRANCE AT SUB-PANEL
NEC 312.5
5. GROUNDS & NEUTRALS TO BE SEPARATE AT SUB-PANEL
NEC 250.24
6. WHERE IS TEP RUNNING SERVICE CONDUCTORS NEED TO MEET CONDUCTOR CLEARANCES ABOVE ROOF PER
NEC 230.26 & 230.24