Permit: T07EL01339

Parcel: 130171840

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T07EL01339

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
11/09/2007 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
11/06/2007 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
08/22/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE ELECTRICAL CONTRACTOR GO THROUGH ALL UNITS AND CHECK ALL ITEMS FROM PREVIOUS INSPECTION
2. HAVE ALL DEVICE PLATES INSTALLED
3. SERVICES NEED TO BE REPLACED. SERVICE AREA IN DISREPAIR. HAVE NEMA 1 ENCLOSURES. SERVICES FALLING OF BUILDINGS. PLYWOOD ENCLOSURES ARE SECURED TO AREA
NEEDS TO BE REPLACED.
07/26/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT 8 ONLY
1. BATHROOM RECEPTACLES TO BE GFI PROTECTED
2. KITCHEN RECEPTACLES TO BE GFI PROTECTED
3. CANNOT HAVE 3 PRONGED RECEPTACLE ON 2 WIRE UNGROUNDED SYSTEM
4. INSTALL SMOKE DETECTORS IN BEDROOMS & OUTSIDE BEDROOMS PER MANUFACTURES INSTRUCTIONS
5. CLOSET LIGHTS DO NOT HAVE PROPER CLEARANCE TO SHELF
6. INSTALL MISSING LIGHT FIXTURES
7. REPAIR ALL OUTSIDE LIGHTS
8. SECURE SERVICES TO BUILDING
9. ADDRESS SERVICES
10. ALL OUTDOOR WIRING TO BE REPAIRED
11. HAVE LADDER TO CHECK ROOF
12. SERVICES MAY NEED TO BE REPLACED. SERVICES FALLING OFF BUILDINGS. HAVE NEMA 1 ENCLOSURES. DO NOT HAVE PROPER CLEARANCES ON SERVICE CONDUCTORS ON NORTH PARKING LOT.