Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUT BOTTOM OF PANEL NEC 110.12 2. EQUIPMENT GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED CONTINUOUSLY -- NEC 250.119 3. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED CONTINUOUSLY - NEC 200.6 4. NEED DETAILED PANEL SCHEDULE - NEC 408.4 5. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3 6. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL 7. POINT OF ATTACHMENT TO BE SO SERVICE CONDUCTORS HAVE PROPER CLEARANCE ABOVE ROOF OF 8' NEC 230.26 & 230.24 8. PLEASE VERIFY PERMITS FOR NEW A/C UNITS |