Permit: T07EL01333

Parcel: 13109116B


Addresses:

5758 E 26TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/26/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CALL BOTH ACTIVITIES @ SAME TIME
2. INSTALL BREAKERS LISTED FOR SQUARE D PANEL
3. STRAP EMT WITHIN 3' OF PANEL
4. STRAP GEC TO BUILDING SURFACE
5. FINISH GROUNDING @ 5760
6. INSTALL PROPER LUG FOR GROUND WIRE @ 5760
7. NEED PANEL DIRECTORY @ 5760
8. INSTALL PENATROX @ 5760
9. INSTALL DEAD FRONT @ 5758
10. CLOSE OPENINGS 5760
11. STRAP SEAL TIGHT @ 5760
02/15/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR