Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/07/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER SWING OVER COMPLETE |
|
| 12/21/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION 2) PANEL NOT DESIGNED TO HAVE HUB INSTALLED ON BOTTOM 3) SECURE 1 1/2" EMT TO BLDG. NEEDS TO BE PROTECTED FROM CURROSION IF BELOW GRADE 4) CLEANOUT DEBRIS FROM BOTTOM OF PANEL 5) HAVE ALL ITEMS COMPLETED BEFORE NEXT INSPECTION TO AVOID REFEE |
|
| 12/20/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH ALL WORK THEN RECALL 2. CALL BOTH PERMITS AT SAME TIME 3. FINISH ITEMS FROM PREVIOUS INSPECTION 4. PVC TO HAVE MIN. 18" OF COVER |
|
| 12/10/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO HAVE DNR REPORT ON SITE FOR NEXT INSPECTION 2. REVISE PERMIT FOR ALL ADDRESSES 3. TIGHTEN WIRES IN METER SECTION 4. INSTALL GROUNDING ELECTRODES & GROUNDING FOR NEW SERVICE 5. RECALL WHEN READY |