Permit: T07EL01326

Parcel: 133145500


Addresses:

6844 E CALLE CERCA

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. A BOND BUSHING IS NEEDED ON SERVICE NIPPLE 250.92
2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
3. CHASE NIPPLE NOT AN APPROVED FITTING WITH LB
4. CANNOT SPLIT CONDUCTORS TO TERMINATE
5. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH AN APPROVED FITTING