Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A BOND BUSHING IS NEEDED ON SERVICE NIPPLE 250.92 2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 3. CHASE NIPPLE NOT AN APPROVED FITTING WITH LB 4. CANNOT SPLIT CONDUCTORS TO TERMINATE 5. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH AN APPROVED FITTING |