| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CALLED PH# PER REQUEST -- NO ANSWER, LEFT MESSAGE WITH E.T.A |
|
| 07/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DEADFRONT MISSING ON PEDESTAL 2. PLUG UNUSED KO ON SIDE 3. INSTALL PERMANENT LABEL FOR #2 ON PEDESTAL. UNIT #2 NOT ON PERMIT 4. PVC CONDUIT SUBJECT TO DAMAGE - INSTALL PROTECTION, PEDESTAL IN MIDDLE OF DRIVEWAY. 5. MOBILE UNIT NOT CONNECTED TO PEDESTAL - SPOKE TO APPLICANT, TOLD HIM UNIT MUST BE CONNECTED TO PEDESTAL. |