Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN |
|
| 08/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ROOF JACK FOR RISER 2. USE A LISTED RISER SUPPORT - HOMEMADE OUT OF SMASHED EMT NOT APPROVED 3. USE 1/4" BOLTS WITH PROPER BACK SUPPORT FOR RISER CONDUIT, CUT PIECES OF PIPE NOT APPROVED 4. HOW DID YOU SPLICE NEW WIRING IN ATTIC, NEED TO VERIFY WATER & GAS BONDING. NEEDS TO BE ACCESSIBLE 5. INSTALL ADDRESS LABEL ON SERVICE AND DEAD FRONT COVER |