Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED LISTED MAST BRACE - NEC 230.28 GO INTO STRUCTURE 2. CAN'T HAVE 2 NEUTRALS UNDER SAME SCREW IN SERVICE NEC 408.21 3. BOND WATER PIPE - CONNECTION TO BE ACCESSIBLE -- 250.104 4. MAKE SURE PANEL DIRECTORY CORRECT -- NEC 408.4 5. PERMIT NEEDED FOR NEW AC 6. SEALING LOCKNUT |