Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE CONDUCTORS DO NOT HAVE PROPER CLEARANCE FROM GROUND -- NEED 10' MIN., 12' OVER PROPERTY NEC 230.24B 2. COPPER TO ALUMINUM SPLICE CONNECTORS MUST BE IDENTIFIED FOR THAT USE (AL/CU) NEC 110.14 3. MAXIMUM 40 AMP ON #6 AL -- NEC 310 4. BOND WATER & GAS PIPES TO SERVICE -- NEC 250.104 5. PROVIDE A POINT OF ATTACHMENT FOR SERVICE DROP NEC 230.26 |