Permit: T07EL01282

Parcel: 136341840


Addresses:

7641 E LAKESIDE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS TO BE MIN. 6' APART - NEC 250.53 & 250.56
2. MARK "SERVICE DISCONNECT" NEC 230.70
3. PROVIDE PENETROX ON ALUMINUM TERMINATIONS
4. CANNOT TWIST ALL GROUNDS TOGETHER & TERMINATE TO ONE TERMINAL. LUG NOT LISTED FOR MULTIPLE TERMINATIONS UNDER ONE TERMINAL - NEC 110.3
5. INSTALL MAIN BONDING JUMPER NEC 250.28
6. CANNOT VERIFY GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS TO GROUNDING ELECTRODE NEC 250.64
7. CANNOT SEE INTO METER ENCLOSURE. SERVICE ENERGIZED PRIOR TO APPROVALS.