Permit: T07EL01274

Parcel: 112030080


Addresses:

2718 E PRINCE RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/24/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) OK POWER-CALL WHEN SWITCH OVER COMPLETE
08/21/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PREVIOUS CORRECTION NOT MADE - GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR OR VIA A BONDING JUMPER -- NOT JUST TO ENCLOSURE
READ NEC 250.24
2. SECURE G.E.C AND WATER BONDING CONDUCTORS TO THE STRUCTURE NOT TIED TO SERVICE RISER - NEC 250.64, 300.11
08/02/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE UFER CONDUCTOR FROM RODS HAS TO BE CONNECTED TO THE NEUTRAL NOT JUST ENCLOSURE
07/30/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE PUT A STANDING PLATFORM IN FRONT OF NEW SERVICE IN ORDER TO INSPECT.