Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK POWER-CALL WHEN SWITCH OVER COMPLETE |
|
| 08/21/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PREVIOUS CORRECTION NOT MADE - GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR OR VIA A BONDING JUMPER -- NOT JUST TO ENCLOSURE READ NEC 250.24 2. SECURE G.E.C AND WATER BONDING CONDUCTORS TO THE STRUCTURE NOT TIED TO SERVICE RISER - NEC 250.64, 300.11 |
|
| 08/02/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE UFER CONDUCTOR FROM RODS HAS TO BE CONNECTED TO THE NEUTRAL NOT JUST ENCLOSURE |
|
| 07/30/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE PUT A STANDING PLATFORM IN FRONT OF NEW SERVICE IN ORDER TO INSPECT. |