Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01263
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND NIPPLE THROUGH BACK OF SUB-PANEL DO NOT HAVE GOOD METAL CONTACT -- NEC 250.96 2. NEED LEVEL WORKING SPACE IN FRONT OF SUB-PANEL BOB CALL ME 954-0161 3. PROTECT WIRE ENTERING & EXITING CONDUITS FOR GARAGE -- NEC 300.4 |