Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP GROUND WIRES TO WALL COMING DOWN FROM SERVICE. 2. CAN ONLY USE ONE #4 COPPER GOING TO BARREL LUG AT GROUND ROD - ITS ONLY LISTED FOR ONE WIRE 3. RE-TIE GROUND TO PHONE SERVICE & CABLE PROPERLY NOTICE: BE ADVISED HOMEMADE MAST SUPPORTS NO LONGER ACCEPTED -- WILL HAVE TO USE LISTED & APPROVED ON YOUR NEXT SERVICE. CORRECT 1 & 2 AND 3 -- RECALL FINAL |