Permit: T07EL01259

Parcel: 123150580


Addresses:

916 E ELM ST #B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/16/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAX. 15 AMP BREAKER ON 14GA CONDUCTOR
2. BURY OR SECURE TO STRUCTURE GROUNDING ELECTRODE CONDUCTOR
3. DO A BETTER JOB OF SECURING SERVICE AND GFI TO STRUCTURE
4. RAINTITE (3R) J-BOX NO LONGER RAINTITE WITH SIDE ENTRIES, GROUND J-BOX WITH EQUIPMENT GROUND
5. HAVE OPEN WIRING TO RIGHT OF SERVICE
6. BOND GAS/WATER PIPES TO SERVICE
7. TIGHTEN GROUND ROD ACORNS.