Permit: T07EL01258

Parcel: 133262620


Addresses:

8354 E BALFOUR DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PROPER SIZE LUG FOR NEUTRAL TO SUB-PANEL NEC 110.3
2. REMOVE OLD SERVICE MAST & CONDUCTORS
3. PROVIDE ACCESS TO SUB-PANEL
ENSURE GROUNDS & NEUTRAL ARE SEPARATED AT SUB-PANEL
NEC 250.24