Permit: T07EL01254

Parcel: 115022860

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01254

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PERMIT PULLED FOR A/C WORK
2) COMPLETE ITEM 1 FROM INSPECTION ON 8/15/07. NEED DISCONNECTING MEANS FOR WATER HEATER-NEC 422.31B
3) ALL OTHER INSPECTION ITEMS CORRECTED
08/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) STILL NEED APPROVED REVISED PLANS
2) TEMPORARY SALES WIRING TO BE SWITCHED OVER AND OR DELETED
3) PREVIOUS CORRECTIONS TO BE COMPLETED
08/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DISCONNECTING MEANS FOR WATER HEATER
NEC 422.31B
2. GROUND J-BOXES NEC 250.148
3. INSTALL ALL DEVICE COVERS
4. HAVE REVERSE POLARITY
5. NEED GFI OR NON-GROUNDING TYPE RECEPTACLE WHERE NO GROUND EXIST

ON ROOF
1. SERVICE RECEPTACLE NOT WORKING, NOT GFI?
HAS BROKEN COVER
2. AC DATA PLATE NOT IDENTIFIED AC DISCONNECT. DOES NOT HAVE PROPER WORKING CLEARANCE IN FRONT (CONDENSATE & EMT) WIRE AC THROUGH FACTORY PROVIDED HOLD TO J-BOX EMT TO BE SECURED TO ROOF.
08/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. A PERMIT IS NEEDED FOR ALL ELECTRICAL WORK
I.E NEW CKTS, NEW AC REPLACE DEVICES, ETC.

WORK TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR
CORRECTIONS TO NUMEROUS TO LIST