Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01247
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ELECTRICAL WIRING IN ENCLOSED GARAGE TO HOUSE IMPROPERLY INSTALLED AT CEILING -- NEEDS TO BE REMOVED AND ADEQUATELY DEAD ENDED 2. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 3. FUSES IN PANEL IN WASH ROOM TO BE 15 AMP OR 20 AMP ACCORDING TO CIRCUIT SIZE 4. COVER ALL RECEPTACLES IN BEDROOMS 5. INSTALL MISSING FIXTURE IN REAR BATHROOM 6. REMOVE WIRING TO CLOSET LIGHT EAST BEDROOM (MIDDLE) 7. PROPERLY SUPPORT ROOF DISCONNECT FOR COOLER CONNECT & RECALL 8. CORRECT WIRING OUTSIDE AT REAR PORCH ON LIGHT AND J-BOX CONNECT ALL ABOVE AND RECALL |