Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07EL01246

Parcel: 138050510

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/28/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) BURY #4 GROUND
2) GROUND J-BOX
3) STRAP 3/4" CONDUIT
4) USE A LISTED RISER SUPPORT, HOMEMADE OUT OF BENT EMT NOT APPROVED
5) RECALL INSPECTION