Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01243
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* THIS ACTIVITY COVERS SERVICE UPGRADE ONLY ALL OTHER NEW WORK WILL REQUIRE SEPARATE PERMIT |
|
10/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING CONNECTOR SHALL NOT BE MADE TO ANY GROUNDED CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS - NEC 250.24 (A)(5) 2. PLEASE VERIFY PERMITS SFOR ALL NEW WORK TO CARWASH 3. PROVIDE PROTECTIVE BUSHINGS ON CONDUCTORS LARGER THAN #4 AWG -- NEC 300.4 4. PLEASE PROVIDE LADDER FOR INSPECTION OF JUNCTION BOX 5. JUNCTION BOX NOT SIZED PROPERLY PER NEC 314.28 |