Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07EL01243
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
10/02/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL FOR INSPECTION WHEN ALL WORK COMPLETED |
|
09/28/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEMS #4 & #6 FROM PREVIOUS INSPECTION 2. LUGS NOT MARKED FOR USE WITH 1/0 CONDUCTORS MARKED 800 MCM - 3/0 |
|
09/24/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE APPROVED SET OF PLANS 2. CHECK ALL CONNECTIONS TIGHT - TORQUE TO MANUFACTURES SPECS 3. BOND CT CABINET PER NEC 250.92 & 250.102 4. BOND SERVICE RISERS PER NEC 250.92 & 250.102 5. BOND CLOSE NIPPLES PER NEC 250.92 & 250.102 6. BOND WIRE WAY PER NEC 250.92 & 250.102 7. VERIFY PVC ABOVE GROUND IS SCHEDULE 80 8. PREVENT OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS - NEC 250.6 9. INSTALL PROTECTIVE BUSHING ON CONDUCTORS THROUGH 2 1/2" PVC NEC 352.46 & 300.4 10. ATTACH LUGS PROPERLY - DO NOT STACK OVER 1/4/20 NUTS 11. MARK "SERVICE DISCONNECTS" PER NEC 230.70 |