Permit: T07EL01243

Parcel: 13416205D


Addresses:

1041 S KOLB RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL01243

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/02/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) RECALL FOR INSPECTION WHEN ALL WORK COMPLETED
09/28/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEMS #4 & #6 FROM PREVIOUS INSPECTION
2. LUGS NOT MARKED FOR USE WITH 1/0 CONDUCTORS MARKED 800 MCM - 3/0
09/24/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE APPROVED SET OF PLANS
2. CHECK ALL CONNECTIONS TIGHT - TORQUE TO MANUFACTURES SPECS
3. BOND CT CABINET PER NEC 250.92 & 250.102
4. BOND SERVICE RISERS PER NEC 250.92 & 250.102
5. BOND CLOSE NIPPLES PER NEC 250.92 & 250.102
6. BOND WIRE WAY PER NEC 250.92 & 250.102
7. VERIFY PVC ABOVE GROUND IS SCHEDULE 80
8. PREVENT OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS - NEC 250.6
9. INSTALL PROTECTIVE BUSHING ON CONDUCTORS
THROUGH 2 1/2" PVC NEC 352.46 & 300.4
10. ATTACH LUGS PROPERLY - DO NOT STACK OVER 1/4/20 NUTS
11. MARK "SERVICE DISCONNECTS" PER NEC 230.70