Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPERLY IDENTIFY NEUTRAL CONDUCTOR TO SUB-PANEL NEC 200.6 2. PROTECT #6 GROUNDING ELECTRODE CONDUCTOR FROM PHYSICAL DAMAGE -- NEC 250.64 3. COMPLETELY DRIVE GROUND RODS PER NEC 250.53 4. BURY GROUNDING CONDUCTOR BETWEEN GROUND RODS. 5. WATER BOND TO BE INSTALLED PER NEC 250.104 & SIZED PER NEC 250.66 6. VERIFY BONDING OF GAS PIPING |