Permit: T07EL01241

Parcel: 134170480


Addresses:

7441 E PRINCETON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONNECT OVERHEAD SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER ENCLOSURE
2. LUG IN JUNCTION BOX RATED FOR 1 WIRE TERMINATION
3. SOUTHWEST GAS REQUIRES 3FT CLEARANCE FROM VACUUM BREAK TO ELECTRIC SERVICE
4. IS TEP GOING TO RELOCATE OVERHEAD SERVICE CONDUCTORS SO THEY DO NOT PASS OVER PORCH ROOF. NEED TO MEET CLEARANCE REQUIREMENTS OF
NEC 230.26 & 230.24
5. CLEARLY MARK BRANCH CIRCUITS PER NEC 408.4