Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IN TRAILER SUB-PANEL NEED MAX 15 AMP ON #14 GA WIRE 2. SEPARATE GROUNDS AND NEUTRALS/TIGHTEN ALL CONNECTIONS 3. INSTALL COVER 4. CORD PLUG CAP IS TO BE MOLDED TYPE -- SEE NEC 552.43B 5. PANEL IS 240V, BUT YOU HAVE 120V CORD? SUB-PANEL PHASE JUMPED WITH #12 WIRE HAVE QUALIFIED ELECTRICIAN MAKE CORRECTIONS |