Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01240

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IN TRAILER SUB-PANEL NEED MAX 15 AMP ON #14 GA WIRE
2. SEPARATE GROUNDS AND NEUTRALS/TIGHTEN ALL CONNECTIONS
3. INSTALL COVER
4. CORD PLUG CAP IS TO BE MOLDED TYPE -- SEE NEC 552.43B
5. PANEL IS 240V, BUT YOU HAVE 120V CORD?
SUB-PANEL PHASE JUMPED WITH #12 WIRE

HAVE QUALIFIED ELECTRICIAN MAKE CORRECTIONS