Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL MAIN BONDING JUMPER PER NEC 250.28 ITS THE GREEN SCREW THAT GOES THROUGH THE NEUTRAL BAR INTO BACK OF PANEL. SEE INSTRUCTIONS ON SIDE OF BACK BOX. 2. INSTALL GFI RECEPTACLE IN WORKMANLIKE MANNER BOX NEEDS TO BE SECURED TO BUILDING SURFACE. NEEDS MORE ROOOM BELOW PANEL TO ALLOW COVER TO BE OPEN 3. HAVE ITEMS CORRECTED BEFORE NEXT INSPECTION TO AVOID PAYING REFEE |
|
| 09/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* STILL NEED TO INSTALL MAIN BONDING ITEM #2 FROM PREVIOUS INSPECTION ON 7/2/07 |
|
| 07/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MARK "SERVICE DISCONNECT" PER NEC 230.70 2. INSTALL MAIN BONDING JUMPER 3. SEAL OPENING IN BACK OF PANEL WHERE WIRES COME THROUGH WITH NON-COMBUSTIBLE MATERIAL 4. SERVICE ENERGIZED PRIOR TO APPROVALS. CANNOT SEE CONNECTIONS IN METER SECTION. CANNOT SEE IF RISER IS BONDED PROPERLY. |