Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) PERMIT OBTAINED FOR INTERIOR WORK #T07CM03111 |
|
| 07/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CONTRACTORS SCOPE OF WORK IS COMPLETE 1. FINISH #7 OF PREVIOUS INSPECTION |
|
| 07/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAINTAIN WORKING CLEARANCE 110.26 2. LABEL BREAKERS PER 408.4 - NO ABBREVIATIONS 3. A BOND BUSHING IS NEEDED ON RISER 4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 5. INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS 6. ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS 7. PLEASE VERIFY PERMITS FOR NEW WORK TO INTERIOR 8. USE APPROVED SPLICE TERMINATIONS FOR GROUNDS IN JUNCTION BOX |
|
| 07/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED -- NO ACCESS |