Permit: T07EL01216

Parcel: 133120260


Addresses:

7760 E SENECA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) PERMIT OBTAINED FOR INTERIOR WORK #T07CM03111
07/24/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CONTRACTORS SCOPE OF WORK IS COMPLETE
1. FINISH #7 OF PREVIOUS INSPECTION
07/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAINTAIN WORKING CLEARANCE 110.26
2. LABEL BREAKERS PER 408.4 - NO ABBREVIATIONS
3. A BOND BUSHING IS NEEDED ON RISER
4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR
5. INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS
6. ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS
7. PLEASE VERIFY PERMITS FOR NEW WORK TO INTERIOR
8. USE APPROVED SPLICE TERMINATIONS FOR GROUNDS IN JUNCTION BOX
07/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED -- NO ACCESS