Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/13/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEM 1, 6, 9, 10 |
|
| 08/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PLEASE VERIFY PERMITS FOR NEW INTERIOR WIRING 2. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 3. INSTALL LOCKNUT CORRECTLY 4. RISER HARDWARE TO BE 1/4" MINIMUM 5. WHITE NOT ALLOWED AS AN UNGROUNDED CONDUCTOR IN A RACEWAY 6. VERIFY PERMIT FOR NEW AC 7. TIGHTEN LOOSE FITTINGS & SUPPORT CONDUIT TO JUNCTION BOX 8. CORRECTLY INSTALL GROUND WIRE UNDER SCREW 9. WIRE NOT TO BE LISTED FOR COPPER & ALUMINUM 10. SECURE CABLE TO BOX 312.5 11. BOX OVERFILLED & MISSING COVER LAUNDRY ROOM |
|
| 07/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CALL FOR FINAL AFTER TIE |