Permit: T07EL01207

Parcel: 121100060


Addresses:

4760 E EDISON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH PREVIOUS ITEM 1, 6, 9, 10
08/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PLEASE VERIFY PERMITS FOR NEW INTERIOR WIRING
2. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS
3. INSTALL LOCKNUT CORRECTLY
4. RISER HARDWARE TO BE 1/4" MINIMUM
5. WHITE NOT ALLOWED AS AN UNGROUNDED
CONDUCTOR IN A RACEWAY
6. VERIFY PERMIT FOR NEW AC
7. TIGHTEN LOOSE FITTINGS & SUPPORT CONDUIT TO JUNCTION BOX
8. CORRECTLY INSTALL GROUND WIRE UNDER SCREW
9. WIRE NOT TO BE LISTED FOR COPPER & ALUMINUM
10. SECURE CABLE TO BOX 312.5
11. BOX OVERFILLED & MISSING COVER LAUNDRY ROOM
07/23/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CALL FOR FINAL AFTER TIE