Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE ITEMS FROM PREVIOUS INSPECTION 2. RECALL WHEN ALL ELECTRIC COMPLETE |
|
| 06/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ROMEX CANNOT BE INSTALLED IN WET LOCATION UNDERGROUND RACEWAYS ARE CONSIDERED WET LOCATION 2. OK UNDERGROUND 1/2" PVC 3. MESSAGE LEFT FOR INSPECTOR WAS BREAKING UP & COULD NOT UNDERSTAND IT. PLEASE LEAVE DETAILED MESSAGE ON HOW TO ENTER COMMUNITY. HAD TO FOLLOW FED EX TRUCK IN 4. PHONE # FOR APPLICANT IS NOT CORRECT |