Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/27/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SEAL ENTRANCE ABOVE CURRENT CARRING PARTS 2. CLEAN SURFACE UNDER GROUND LUG - 250.12 |
|
| 08/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) USE APPROVED FITTING WITH L.B. 2) GROUND JUNCTION BOX ENCLOSURE 3) PLEASE UNCOVER UNDERGROUND CONDUITS FOR INSPECTION 4) CANNOT ENTER THROUGH TOP END WALL OF PANEL 5) FILL UNUSED OPENINGS IN PANEL 6) LABEL ALL BREAKERS 7) RISER NEEDS SUPPORT |