Permit: T07EL01203

Parcel: 12111190A


Addresses:

4826 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/27/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SEAL ENTRANCE ABOVE CURRENT CARRING PARTS
2. CLEAN SURFACE UNDER GROUND LUG - 250.12
08/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) USE APPROVED FITTING WITH L.B.
2) GROUND JUNCTION BOX ENCLOSURE
3) PLEASE UNCOVER UNDERGROUND CONDUITS FOR INSPECTION
4) CANNOT ENTER THROUGH TOP END WALL OF PANEL
5) FILL UNUSED OPENINGS IN PANEL
6) LABEL ALL BREAKERS
7) RISER NEEDS SUPPORT