Inspection History Details
Permit: T07EL01200
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GROUND WIRE AT LUG IN TRANSFORMER NOT SET RIGHT USE CORRECT TYPE OF LUG |
|
| 07/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PLANS/PERMIT NOT POSTED ON SITE |
|
| 07/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CALLED PAT, MOUNTAIN POWER - LEFT MESSAGE 2. RACEWAYS NOT COMPLETE INTO X-FORMER, CONDUCTORS ARE EXPOSED UNDER X-FORMER 3. PLANS/PERMIT? 4. RECALL WHEN ON SITE - REMOVE X-FORMER COVERS FOR INSPECTION |
|
| 07/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TRANSFORMER TO HAVE WEATHER SHIELDS 2. TERMINATIONS IN TRANSFORMER NOT MADE 3. NEED TO PROTECT WIRING COMING OUT OF CONDUITS INTO BOTTOM OF TRANSFORMER FROM ABRASION 4. THERE IS A PROBLEM WITH LEAVING BOTTOMS OF TRANSFORMER OPEN -- ENERGIZED CABLES CAN BE REACHED. |
|
| 07/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/02/2007 | ELECTRIC - FINAL | Not ready for Inspection | NO SECONDARY LOAD ON 200A BKR NO COLOR CODING ON 480V CONDUCTORS |
|
| 06/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SAME ITEMS AS YESTERDAYS WRITE UP 2. 480V WIRING FROM SECONDARY METRO TERMINALS AND INSIDE CABINET TO BE IDENTIFIED AS 480V 3. MISSING WIRING INSIDE CABINET FROM LOAD END OF CIRCUIT BREAKER TO SECONDARY BREAKERS |
|
| 06/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 480V WIRING HAS TO BE COLOR MARKED 2. MISSING WIRING ON LOAD SIDE OF MAIN BREAKER |