Permit: T07EL01200

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GROUND WIRE AT LUG IN TRANSFORMER
NOT SET RIGHT
USE CORRECT TYPE OF LUG
07/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PLANS/PERMIT NOT POSTED ON SITE
07/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CALLED PAT, MOUNTAIN POWER - LEFT MESSAGE
2. RACEWAYS NOT COMPLETE INTO X-FORMER, CONDUCTORS ARE EXPOSED UNDER X-FORMER
3. PLANS/PERMIT?
4. RECALL WHEN ON SITE - REMOVE X-FORMER COVERS FOR INSPECTION
07/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TRANSFORMER TO HAVE WEATHER SHIELDS
2. TERMINATIONS IN TRANSFORMER NOT MADE
3. NEED TO PROTECT WIRING COMING OUT OF CONDUITS INTO BOTTOM OF TRANSFORMER FROM ABRASION
4. THERE IS A PROBLEM WITH LEAVING BOTTOMS OF TRANSFORMER OPEN -- ENERGIZED CABLES CAN BE REACHED.
07/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/02/2007 ELECTRIC - FINAL Not ready for Inspection NO SECONDARY LOAD ON 200A BKR
NO COLOR CODING ON 480V CONDUCTORS
06/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SAME ITEMS AS YESTERDAYS WRITE UP
2. 480V WIRING FROM SECONDARY METRO TERMINALS AND INSIDE CABINET TO BE IDENTIFIED AS 480V
3. MISSING WIRING INSIDE CABINET FROM LOAD END OF CIRCUIT BREAKER TO SECONDARY BREAKERS
06/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 480V WIRING HAS TO BE COLOR MARKED
2. MISSING WIRING ON LOAD SIDE OF MAIN BREAKER