Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BARE CONDUCTOR ON OLD SERVICE CABLE IS NEUTRAL CONDUCTOR & NEEDS TO BE IDENTIFIED AS REQUIRED PER NEC 200.6 2. NEW CONDUCTOR RUN TO BARE CONDUCTOR IS NOT EQUIPMENT GROUNDING CONDUCTOR. IT IS NEUTRAL CONDUCTOR & NEEDS TO BE IDENTIFIED PER NEC 200.6 3. POINT OF ATTACHMENT TO BE SO SERVICE CONDUCTOR CLEARANCES ARE MET. NEED 8' ABOVE ROOFS. NEC 230.26 AND NEC 230.24 |