Permit: T07EL01196

Parcel: 134220290


Addresses:

6707 E COOPER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BARE CONDUCTOR ON OLD SERVICE CABLE IS NEUTRAL CONDUCTOR & NEEDS TO BE IDENTIFIED AS REQUIRED PER NEC 200.6
2. NEW CONDUCTOR RUN TO BARE CONDUCTOR IS NOT EQUIPMENT GROUNDING CONDUCTOR. IT IS NEUTRAL CONDUCTOR & NEEDS TO BE IDENTIFIED PER NEC 200.6
3. POINT OF ATTACHMENT TO BE SO SERVICE CONDUCTOR CLEARANCES ARE MET. NEED 8' ABOVE ROOFS. NEC 230.26
AND NEC 230.24