Permit: T07EL01189

Parcel: 138060680

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
07/10/2007 ELECTRIC - RECONNECT Approved APPROVED OK TO CLEAR WILL NOTIFY TEP
07/09/2007 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1. NEED 2 CIRCUIT BREAK COVERS AT PNL
2. SEAL HOLE OUTSIDE SERVICE
3. INSTALL PROTECTIVE INSULATION AROUND WIRING IN PNL
4. REMOVE PORCH WIRING TO LIGHT
07/05/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROOF WIRING RECEPTACLE TO COOLER REPAIR AND INSTALL A WEATHERPROOF COVER
2. INSTALL DEAD FRONT COVER ON SERVICE
3. INSTALL BUSHING IN SERVICE PANEL WHERE WIRES COME THRU WALL
4. CORRECTLY SET CIRCUIT BREAKERS INTO PLACE
5. REPAIR WIRING TO OUTSIDE PORCH LIGHT
6. INSIDE -- REPLACE BATTERIES FOR SMOKE DETECTORS
AND INSTALL COVERS ON RECEPTACLES IN BEDROOMS MISSING COVERS.
07/02/2007 ELECTRIC - RECONNECT Denied HOUSE HAS TO BE OPEN FOR INSPECTION
ALSO, NEED ACCESS TO BACKYARD TO CHECK SERVICE