Permit: T07EL01188

Parcel: 115171740


Addresses:

1326 W YAVAPAI ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED METER OPEN FOR INSPECTION
2. BOND SERVICE NIPPLE
3. NEED HOLD DOWN DEVICE FOR BACKFED MAIN BREAKER
4. BOND WATER & GAS (IF ANY) TO SERVICE
5. PANEL DIRECTORY NOT CORRECT
6. BREAKERS (TWIN BOTTOM RIGHT) NEED TO SHOW AMPERAGE RATING
7. INSTALL 15 AMP BREAKERS ON 20 AMP CKT'S UNLESS YOU CAN VERIFY THAT THEY ARE #12 COPPER ALL THE WAY THRU THE CKT. I SEE 14GA CONDUCTORS