Permit: T07EL01167

Parcel: 128050060


Addresses:

865 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PANEL DIRECTORY PER NEC 408.4
2. SECURE #4 TO BUILDING SURFACE OR BURY IT -- NEC 250.64
3. BELL BOX TO BE RIGIDLY & SECURELY FASTENED IN
PLACE -- NEC 314.23
4. INSTALL IN USE COVER (BUBBLE COVER) ON RECEPTACLE UNDER PANEL -- NEC 406.8
5. NEED TO HAVE ACCESS TO INTERIOR AT HOME TO INSPECT NEW PANEL FEEDER & PANEL
6. WHERE IS NEUTRAL CONDUCTOR TO SUB-PANEL
NEUTRAL CONDUCTOR TO MEET REQUIREMENTS OF NEC 200
7. INSTALL BRANCH CIRCUIT CONDUCTORS TO PANEL RECEPTACLE IN NEAT & WORKMANLIKE MANNER -- NEC 110.12
8. PLEASE VERIFY PERMITS FOR WORK TAKING PLACE INSIDE HOME
9. WHAT SIZE SER CABLE IS INSTALLED. #8 IS ONLY GOOD FOR 30 AMP & #6 FOR 40 AMP FOR 60 DEG. COLUMN & 40 AMP FOR #8 & 50 AMP #6 FOR 75 DEG. COLUMN -- NEC 338.10 &
NEC 110.14 & NEC 310.16
07/02/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*