Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR INCR RESIDENTIAL |
|
| 06/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND GAS PIPING ON HOUSE SIDE OF METER. 2. GROUND LUG IN GUTTER NOT LISTED FOR MULTIPLE CONNECTIONS -- NEC 110.3 3. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTION - NEC 250.8 4. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED CONTINUOUSLY -- NEC 200.6 5. CHECK NEUTRAL CONNECTIONS AT PANEL 6. #8 AWG GOOD FOR 50 AMP MAX - NEC 110.14 & 310.16 7. INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT AND MINNIE -- NEC 230.28 8. CHECK FITTINGS & LOCKNUTS TIGHT 9. CONNECT SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION - NEC 110.3 10. NO ABBREVIATIONS ON PANEL DIRECTORY - 408.4 11. CHECK 12' CLEARANCE TO GROUND ON SERVICE DROP NEC 230.26 & 230.24 |