Permit: T07EL01165

Parcel: 134244010


Addresses:

6337 E BAYLOR DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK TO CLEAR
INCR
RESIDENTIAL
06/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GAS PIPING ON HOUSE SIDE OF METER.
2. GROUND LUG IN GUTTER NOT LISTED FOR MULTIPLE CONNECTIONS -- NEC 110.3
3. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTION - NEC 250.8
4. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED CONTINUOUSLY -- NEC 200.6
5. CHECK NEUTRAL CONNECTIONS AT PANEL
6. #8 AWG GOOD FOR 50 AMP MAX - NEC 110.14 & 310.16
7. INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT AND MINNIE -- NEC 230.28
8. CHECK FITTINGS & LOCKNUTS TIGHT
9. CONNECT SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION - NEC 110.3
10. NO ABBREVIATIONS ON PANEL DIRECTORY - 408.4
11. CHECK 12' CLEARANCE TO GROUND ON SERVICE DROP
NEC 230.26 & 230.24