Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE CONDUCTORS TO BE MIN. 8' ABOVE ROOF 2. USE LISTED MAST BRACE AND AIM IN DIRECTION OF SERVICE DROP. 3. NEED PERMIT FOR NEW AC 4. PROVIDE GROUND RODS FOR SERVICE, BOND GAS & WATER PIPE. 5. #8 COPPER CLAD SUB-PANEL FEEDER TO BE 30 AMP. MAX. |