Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T07EL01162
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 08/10/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) EQUIPMENT GROUND (#4 CU) ADDED. OK TO COVER TRENCH. NEUTRAL TO FLOAT (NEC 250.32B) WHEN MAKING UP PEDESTALS. HAVE PANELS OPEN FOR INSPECTION BEFORE YOU ENERGIZE |
|
| 08/03/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* JIM 603-0336 1. SPEAK WITH YOUR ENGINEER OF RECORD ABOUT WHY THERE IS NO EQUIPMENT GROUND RAN WITH FEEDERS SEE NEC (2002) 230.32B YOU HAVE METALLIC PATHS BETWEEN UNITS |
|
| 07/31/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* NOTES: GROUND ELECTRODE CONDUCTOR TO BE TERMINATED INSIDE LOAD SECTION AT NEUTRAL BAR IN PEDESTAL PER 250.24 |
|
| 07/20/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH UNDERGROUND WIRING 2. GROUND RODS MISSING IN SOME LOCATIONS AND ALSO NEED TO BE A MINIMUM OF 6' APART FROM ANY OTHER GROUND ROD - 250.56, 250.53B 3. VERIFY WHY THERE IS NO EQUIPMENT GROUND RAN WITH FEEDERS -- NEC 250.32B 1, 2? |