Permit: T07EL01160

Parcel: 124070830


Addresses:

810 E 9TH ST #01


Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL01160

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
11/29/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
RECALL AFTER CROSSOVER
11/23/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1. COMPLETE ITEM #1 FROM INSPECTION ON 7/27/07
2. RECALL AFTER TEP TIE IN & SWING OVER COMPLETE
07/27/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GAS PIPING TO EACH UNIT -- NEC 250.104
2. NEED TO BOND WATER PIPING TO EACH UNIT - 250.104
3. CONNECT GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL BUS. - NEC 250.24
4. PLEASE PROVIDE INFORMATION ON GROUND CLAMPS USED AT GROUND RODS. THAT THEY ARE SUITABLE FOR DIRECT BURY & FOR USE ON GROUND RODS -- NEC 250.70
5. REMOVE PAINT A GROUND CLAMP CONNECTIONS ON
GAS PIPE -- NEC 250.12
6. GROUND BAR TERMINALS NOT LISTED OR MARKED FOR 2 WIRE TERMINATION - NEC 110.3
7. DO NOT HAVE PROPER WORKING CLEARANCES AT
UNIT PANELS -- NEC 110.26
8. REMOVE DEBRIS FROM BOTTOM OF PANEL