Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07EL01160
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* RECALL AFTER CROSSOVER |
|
11/23/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. COMPLETE ITEM #1 FROM INSPECTION ON 7/27/07 2. RECALL AFTER TEP TIE IN & SWING OVER COMPLETE |
|
07/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND GAS PIPING TO EACH UNIT -- NEC 250.104 2. NEED TO BOND WATER PIPING TO EACH UNIT - 250.104 3. CONNECT GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL BUS. - NEC 250.24 4. PLEASE PROVIDE INFORMATION ON GROUND CLAMPS USED AT GROUND RODS. THAT THEY ARE SUITABLE FOR DIRECT BURY & FOR USE ON GROUND RODS -- NEC 250.70 5. REMOVE PAINT A GROUND CLAMP CONNECTIONS ON GAS PIPE -- NEC 250.12 6. GROUND BAR TERMINALS NOT LISTED OR MARKED FOR 2 WIRE TERMINATION - NEC 110.3 7. DO NOT HAVE PROPER WORKING CLEARANCES AT UNIT PANELS -- NEC 110.26 8. REMOVE DEBRIS FROM BOTTOM OF PANEL |