Permit: T07EL01155

Parcel: 126151560


Addresses:

4358 E TIMROD ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/02/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*.
1) STILL NEED TO INSTALL BREAKERS LISTED FOR USE IN SIEMENS SERVICE PANEL
2) HAVE MURRAY AND GE BREAKERS INSTALLED NEC 110.3
07/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ITEMS 10 & 11 FROM PREVIOUS INSP. ON 6/19/07
06/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL OPEN KNOCKOUT AT SUB-PANEL -- NEC 110.12
2. CANNOT USE SHEETMETAL SCREWS SOR CONNECTION OF GROUND BAR -- NEC 250.8
3. INSTALL GROUND BAR IN ACCORDANCE WITH MANUFACTURES INSTRUCTIONS & IN WORKMANLIKE MANNER
NEC 110.3 & 110.12
4. GROUNDING CONDUCTORS #6 & SMALLER TO BE MARKED CONTINUOUSLY NEC 250.119
5. ROMEX WIRES AT SUB-PANEL TO BE CONNECTED TO PANEL USING CONNECTORS - NEC 312.5
6. STAPLE ROMEX WIRES AT SUB PANEL & PROTECT FROM PHYSICAL DAMAGE NEC 300
7. IDENTIFY GROUND & NEUTRAL CONDUCTORS TO DRYER PER NEC 250.119 & 200.6
8. 1" EMT HAS KINKS IN IT AT BENDS NEC 358.24
9. VERIFY PIPE FILL ON FEEDER TO SUB-PANEL IT APPEARS TO BE OVERFILLED NEC CHAPTER 9
10. INSTALL BREAKERS LISTED FOR USE IN PANEL NEC 110.3
11. VERIFY PERMIT FOR NEW ROOFTOP AC UNIT