Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T07EL01150
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2007 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 06/20/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECONNECT 3/4" EMT TO PANEL & TIGHTEN FITTINGS 2. IMPROPERLY TAPPED SURGE SURPRESSOR 3. MARK "SERVICE DISCONNECT" 4. LABEL BREAKERS IN PANEL 5. OUTDOOR LIGHT POWERED WITH ZIP CORD 6. REPAIR ROOFTOP WIRING USE WEATHERPROOF FITTINGS AND BOXES 7. CHECK LIGHTS OUTSIDE FRONT OF UNIT 8. OPEN JUNCTION BOXES AND CUT MC CABLE THROUGHOUT UNIT 9. SEAL OPEN KNOCKOUTS 10. ONE NEUTRAL PER TERMINAL AT PANELS 11. GROUNDS & NEUTRALS TO BE SEPARATE AT SUB-PANELS 12. OPEN SPLICES THROUGHOUT UNIT 13. PANELS TO BE PROPERLY SECURED 14. BACK FED BREAKERS TO BE SECURED TO PANELS 15. MISSING WALL PLATES 16. PANEL COVER BEING BLOCKED BY 1/2" EMT 17. BLANK OPEN BREAKER POSITIONS AT PANELS HAVE LICENSED ELECTRICAL CONTRACTOR GO THROUGH UNIT AND REPAIR NUMEROUS VIOLATIONS AND HAZARDS MAY NOT BE COMPLETE LIST. |