Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01139
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IDENTIFY UNIT # ON UNIT 2) NEED SMOKE DETECTOR EACH BEDROOM AND HALLWAY 3) INSTALL PROPER SIZE FUSES IN HALL PANEL (15 AMP) 4) INSTALL ALL COVER PLATES 5) REMOVE LIGHT/CORD OVER SINK 6) HAVE OPEN WIRING HALL CEILING 7) RECEPTACLES TO BE OF THE NON GROUNDING TYPE OR GFI PROTECTED WHERE NO EQUIPMENT GROUND EXIST. ALSO RECEPTACLES TO BE FLUSH TO SURFACE, NOT SET BACK 8) WORK TO BE DONE BY A QUALIFIED ELECTRICIAN |